The T9482 analog output module delivers eight isolated 4–20 mA current output channels. Each channel operates as a current sink to field devices. In simplex mode, each channel supplies the full current demand. In dual-module mode, each channel provides half the required current. This design improves fault tolerance and system reliability. The module includes a 32-bit RISC processor and fast-access memory.This investigation includes various modules and establishes compliance requirements for use in both non-hazardous and hazardous environments. The AADvance controller is designed to meet non-safety business needs as well as SIL 2 and SIL 3 safety-related system requirements. Furthermore, its robust built-in redundancy significantly enhances system availability and reliability.
Technical specifications
Model: T9482
Analog Output Channels: 8 isolated, current sink type
Output Range: 4–20 mA
Output Voltage (Compliance): 18–32 V DC
Maximum Voltage (No Damage): 60 V DC
Maximum Load Impedance: 0–750 Ω
Update Rate: 10 ms per channel
Resolution: 15-bit control, 13-bit monitoring
Accuracy: ±0.5% of full scale (typical)
Isolation Voltage: 1500 V DC between channels
Processor: 32-bit RISC
Memory: 64 MB RAM, 64 MB flash
Power Supply: Redundant +24 V DC (18–32 V DC range)
Power Dissipation: 3.6 W (typical), 20 W (maximum)
Supported Protocols: Ethernet, Modbus, Profibus
I/O Capacity: Up to 16 modules per rack
Operating Temperature: -20°C to +60°C
Key Features
- Eight Fully Isolated Outputs:Each of the eight analog output channels is individually isolated, helping to prevent ground loops and electrical interference across critical process control signals.
- High-Accuracy Signal Conversion:Designed for precise current or voltage output, the T9482 ensures stable and accurate analog signals for demanding industrial automation tasks.
- Enhanced Reliability for Safety Systems:Engineered for fault-tolerant ICS Triplex architectures, the module maintains continuous operation even in high-availability or safety-critical environments.
- Flexible Output Configuration:Supports a wide range of output ranges (e.g., 4–20 mA or 0–10 V) to match various field device requirements without extra hardware.
- Robust Industrial Design:Built to endure harsh plant conditions-such as electrical noise, vibration, and temperature fluctuations-making it ideal for power generation, oil & gas, and heavy process industries.
Is Rockwell ICS Triplex T9482 not the part you are wanting?
Check out the rest of our website to see what else we have to offer!
Recommended products
| SPIIT13 | 12-104-531 | AR2N72PA5300002 |
| SPBRC400 | 12-009-888 | AAR145-S03 |
| SPHSS03 | 12-013-021 | NFLR121-S51 |
| SPDSM04 | 00-0F-9E-F6-51-54 55254 | ALR121-S00 |
| SPSED01 | 857804C | AAR181-S03 |
| SPIET800 | 00C6CC1-1700 | AAI543-S03 |
| SPICT13A | DFS21B | ADV551-P03 |
| SPSET01 | CPX 18-22-91-A1 | ADV551-P50 |
| IMMPI01 | GOV93-2500-604312M | ADV551-P00 |
| IMDSI14 | Ha-VIS aCon 2050GBT-A | SDV531-L23 |
| SPBRC300 | CP6203-0021-0010 | SAI533-H33/PRP |
| SPBRC300 | 9122-IS-CM | NFLR121-S51 |
| IMASI23 | FQ2-S15100F | ASI133-S00 |
| IMDS014 | AFO5100 | ADV151-E63 |
| INNIS21 | HCMCIF-0 | 0570685 |