DeltaV DCS CHARMs
A signal-specific CHARM mounts on its compatible terminal block and baseplate. A CIOC handles communication between the CHARM channels and DeltaV controllers.
DeltaV maintenance parts include M-series and S-series controllers, traditional input/output cards, I/O carriers, LocalBus connections and CHARMs Electronic Marshalling. Safety-system installations use separate DeltaV SIS logic solvers and LS-CHARM assemblies. The correct spare depends on the existing hardware architecture, not just the DeltaV brand or a similar connector.
We source parts by their complete KJ, 12P, VE, SS or other manufacturer identifiers as applicable. Match the module revision, DeltaV release, channel function and its carrier, terminal or solver arrangement before specifying an alternative.
| DeltaV architecture | What connects together | Match before ordering |
|---|---|---|
| M-series / S-series I/O | I/O card, compatible carrier, termination block and LocalBus hardware | Module label, output or input type, installed carrier and DeltaV release |
| DCS Electronic Marshalling | Field terminal, signal-specific CHARM, baseplate and CHARM I/O Card (CIOC) | CHARM type, CIOC, terminal configuration and field-signal requirements |
| SIS Electronic Marshalling | LS-CHARM channel hardware and CHARMs Smart Logic Solver (CSLS) | SIS solver family, LS-CHARM type, safety wiring and approved system configuration |
KJ3001X1-BG1 identifies a DeltaV discrete output card family. Emerson lists the VE4002S1T1B1 configuration as an eight-channel, 24 V DC isolated discrete output card with a standard I/O termination block. Match the existing output card and its specific terminal hardware as a pair.
Check the 12P0557X... suffix on the installed KJ3001X1-BG1 label. Do not treat 12P0557X122, 12P0557X152 or 12P0557X162 as interchangeable without model-specific confirmation from Emerson.
Before replacement: confirm the terminal block, output wiring, isolation requirements and exact card revision. Appearance alone does not establish the correct assembly.
KJ4001X1-HA1 / 12P0949X042 is a horizontal LocalBus cable extender for the DeltaV carrier arrangement. It connects I/O carrier sections and is not a discrete-output card or an Ovation controller component.
Compare the extender's complete marking, mating connector and carrier layout. Disconnect or replace LocalBus hardware only under the applicable DeltaV maintenance instructions and site isolation procedure.
KJ4001X1-HA1 LocalBus connector and molded cable assembly.
A signal-specific CHARM mounts on its compatible terminal block and baseplate. A CIOC handles communication between the CHARM channels and DeltaV controllers.
LS-CHARMs are safety-system I/O channels associated with a CSLS logic solver, not ordinary DCS CIOC channels. Safety wiring and approvals remain system-specific.
Emerson offers both DCS Electronic Marshalling and separate SIS Electronic Marshalling architectures. The type of CHARM, solver or CIOC, terminal and system release must match the installed design.
The SLS 1508 is a DeltaV SIS smart logic solver with software-configurable I/O. A CSLS provides safety logic solving and I/O processing with LS-CHARM channels. Neither the SLS 1508 nor a CSLS is replaced by an ordinary M-series output card or a DCS CHARM.
Confirm simplex or redundant hardware, the safety-system release, termination equipment and approved configuration before selecting a solver or an LS-CHARM assembly.
Provide the full KJ, 12P and VE markings when shown, carrier type, signal rating and module revision.
Specify the CHARM type, CIOC, terminal block, DeltaV release and connected field signal.
Identify SLS or CSLS, LS-CHARM if applicable, redundant arrangement and safety terminal hardware.
Check extender part number, left/right or horizontal position, connectors and the installed carrier arrangement.
A KJ3001X1-BG1 family designation alone does not confirm the full assembly. Match the 12P suffix and revision on the existing label, then verify the corresponding card and termination configuration.
No. A CSLS uses the specified LS-CHARM safety I/O components. The DCS CIOC/CHARM configuration and the SIS CSLS/LS-CHARM configuration require different, approved component selections.
Provide the full extender code, a connector photo and the installed carrier layout. Identify the mating LocalBus hardware and verify the relevant DeltaV maintenance and power-isolation requirements.
Send the complete manufacturer marking, hardware revision, required quantity, condition and destination country . For an installed replacement, include the DeltaV release and a clear label photo of the card, LocalBus extender, CHARM/CIOC or safety solver and its mating hardware.
Submit DeltaV Parts RFQAs one of the leading emerson deltav manufacturers and suppliers, we warmly welcome you to wholesale discount emerson deltav from our factory. All our products are with high quality and competitive price.
process control systems, compressors, transformersDisclaimer:
PLCleader sells new and surplus products and develops channels for purchasing such products. This website has not been approved or recognized by any of the listed manufacturers or trademarks.
PLCleader is not an authorized distributor, dealer, or representative of the products displayed on this website. All product names, trademarks, brands, and logos used on this website are the property of their respective owners. The description, explanation, or sale of products with these names, trademarks, brands, and logos is for identification purposes only and is not intended to indicate any association with or authorization from any rights holder.