Honeywell 10310/3/1 Earth Leakage Detector
Honeywell 10310/3/1 (also listed as 10310-3-1) is an Earth Leakage Detector for 24 V DC systems. It detects an earth-fault condition, latches the fault indication and de-energizes its status relay until reset.
The module has DC, 1 Hz and 1/4 Hz operating modes, a manual TEST/RESET control and an external reset input. It is a dedicated earth-fault monitoring device, not a programmable controller or digital I/O card.
What Happens When an Earth Fault Occurs?
During normal monitoring, the ELD connects the earth reference at -12 V DC relative to the supply 0 V. A detected earth fault sets the internal latch and causes the fault relay to de-energize. The latched condition is retained until a manual or electrical reset is applied.
A reference connection monitors unwanted current paths to earth.
A fault sets the internal latch; the red FAULT indicator identifies the condition.
The status relay de-energizes. The indication remains latched until reset.
The relay contact must be matched to the receiving alarm or monitoring circuit. It is a fault-status output, not a general-purpose high-power switching output.
Electrical, Relay and Mounting Specifications
| Specification | Honeywell 10310/3/1 Rating |
|---|---|
| Power Supply | 24 V DC; maximum 45 mA |
| Earth-Fault Threshold | 5.5 mA ±1 mA |
| Earth Reference, No Fault | -12 V DC relative to supply 0 V |
| Maximum Earth Current | 25–32 mA |
| Electrical Reset Input | 18–70 V DC; 1.1 mA at 24 V DC |
| Maximum Relay Output Voltage | 36 V DC / 30 V AC |
| Maximum Relay Output Current | 2 A |
| Output Isolation | 1500 V DC / 1000 V AC |
| Earth Terminal Tightening Torque | 1 N·m |
| Operating Temperature | -5°C to +50°C |
| Storage Temperature | -25°C to +80°C |
| Dimensions (L × W × H) | 70 × 45 × 110 mm |
| DIN Rail | TS35 × 7.5; maximum 46 mm rail length occupied |
Relay rating: Do not substitute the higher contact ratings published for other 10310 ELD variants. The 10310/3/1 output is rated at 36 V DC / 30 V AC and 2 A maximum.
Choose the Correct Earth-Reference Mode
Switch 1 determines whether the -12 V earth reference is connected continuously or intermittently. Honeywell identifies DC as the normal operating position.
Continuous earth-reference connection for normal monitoring.
Intermittent connection for circuits with solenoids or relays that could remain energized by the negative earth voltage.
Intermittent connection used for earth-fault location with a suitable current clamp.
The green MODE LED flashes at the selected frequency when the switch is set to 1 Hz or 1/4 Hz. Operating-mode selection should follow the original system design and maintenance procedures.
Earth1 / Earth2 Connections and the TEST Function
The Earth1 and Earth2 connections are significant because the TEST function can check more than the detector electronics. An internal 1.5 kΩ test path uses the Earth2 connection to help verify the earth circuit.
With independent earth leads, the preferred Honeywell wiring arrangement allows the Earth1 connection to be included in the self-test.
Linking Earth1 and Earth2 reduces wiring, but a break in the shared earth wire cannot be detected during the test.
Functional comparison only; not a field-wiring diagram. Use Honeywell's connection drawings for terminal positions and installation.
TEST
The test arrangement checks the ELD fault response and, with the separate earth connection, the associated earth circuit. A disconnected earth path can prevent the latch from setting during the test.
RESET
A latched fault can be reset using switch 2 or a high level at the reset input. The cause of the earth fault must be assessed before the equipment is returned to service.
Maintenance: Earth-fault testing, earth-wire changes and fault reset must follow the site's approved electrical and safety procedures. The preferred connection and single-wire alternative are not equally capable of detecting an open earth lead.
Installation and Exact-Part Replacement
The detector mounts on a TS35 × 7.5 DIN rail and uses a 24 V DC supply. For a replacement, compare the installed module label and hardware revision, available cabinet space, earth terminals, reset input and relay contact wiring before changing the device.
Physical and Electrical Fit
- Complete 10310/3/1 type identification
- TS35 DIN-rail position and access
- +24 V, 0 V and earth connections
- Reset and relay terminal assignments
System Verification
- Installed safety-system design and revision
- Selected DC / 1 Hz / 1/4 Hz mode
- Fault indication and reset behavior
- Approved inspection and proof-test procedure
10310/1/1, 10310/2/1 and 10310/3/1 have distinct published specifications. A similar appearance or earth-leakage function does not establish direct interchangeability. We identify quoted replacements by the exact part number and available nameplate details.
Honeywell Documentation and Related Components
Honeywell's Safety Manager Hardware Reference, section 13.3 , includes the ELD block diagram, approved connection examples and module-specific technical ratings.
Frequently Asked Questions
10310/3/1 is Honeywell's type notation; 10310-3-1 is commonly used in part listings and URLs. The actual module label and revision should still be checked.
The preferred separate-earth arrangement allows the Earth1 path to be checked during TEST. With a single linked earth wire, an open wire may go undetected by that test.
The relay de-energizes when an earth fault sets the internal latch. The latched state remains until a manual reset or a suitable electrical reset signal is applied.
Honeywell identifies 1/4 Hz mode for earth-fault location using a suitable current clamp. It is not the normal continuous-monitoring setting.
Not without an engineering review. Compare the exact variant, output-contact ratings, reset interface, earth wiring, physical installation and approved system configuration before accepting a different module.
Request Honeywell 10310/3/1
Send us the exact Honeywell type number, hardware revision, required quantity, item condition and destination country. Nameplate photographs and existing ELD connection details can help confirm the requested replacement.
We confirm availability, origin, warranty and delivery terms for the specific item offered rather than treating them as fixed specifications of the module.
Submit 10310/3/1 RFQHot Tags: Honeywell 10310/3/1, 10310-3-1, Honeywell earth leakage detector, 24V DC ELD, earth fault relay, Honeywell FSC parts, Safety Manager ELD, maintenance services, global sourcing, aluminum, nickel, warehousing services, valve actuators