Honeywell 10310/3/1 Earth Leakage Detector

• Honeywell 10310/3/1 Earth Leakage Detector
• For 24 V DC earth-fault monitoring
• 5.5 mA ±1 mA earth-fault threshold
• 36 V DC / 30 V AC, 2 A relay contact
• DC, 1 Hz and 1/4 Hz selectable modes
• TEST/RESET with Earth1 and Earth2 terminals
• TS35 × 7.5 DIN-rail installation
Send Inquiry
Description

Honeywell 10310/3/1 Earth Leakage Detector

Honeywell 10310/3/1 (also listed as 10310-3-1) is an Earth Leakage Detector for 24 V DC systems. It detects an earth-fault condition, latches the fault indication and de-energizes its status relay until reset.

The module has DC, 1 Hz and 1/4 Hz operating modes, a manual TEST/RESET control and an external reset input. It is a dedicated earth-fault monitoring device, not a programmable controller or digital I/O card.

24 V DC 5.5 mA ±1 mA Relay Fault Output TEST / RESET TS35 DIN Rail
Request 10310/3/1 Quote

What Happens When an Earth Fault Occurs?

During normal monitoring, the ELD connects the earth reference at -12 V DC relative to the supply 0 V. A detected earth fault sets the internal latch and causes the fault relay to de-energize. The latched condition is retained until a manual or electrical reset is applied.

Earth Monitoring

A reference connection monitors unwanted current paths to earth.

Fault Latch

A fault sets the internal latch; the red FAULT indicator identifies the condition.

Relay Response

The status relay de-energizes. The indication remains latched until reset.

The relay contact must be matched to the receiving alarm or monitoring circuit. It is a fault-status output, not a general-purpose high-power switching output.

Electrical, Relay and Mounting Specifications

Specification Honeywell 10310/3/1 Rating
Power Supply 24 V DC; maximum 45 mA
Earth-Fault Threshold 5.5 mA ±1 mA
Earth Reference, No Fault -12 V DC relative to supply 0 V
Maximum Earth Current 25–32 mA
Electrical Reset Input 18–70 V DC; 1.1 mA at 24 V DC
Maximum Relay Output Voltage 36 V DC / 30 V AC
Maximum Relay Output Current 2 A
Output Isolation 1500 V DC / 1000 V AC
Earth Terminal Tightening Torque 1 N·m
Operating Temperature -5°C to +50°C
Storage Temperature -25°C to +80°C
Dimensions (L × W × H) 70 × 45 × 110 mm
DIN Rail TS35 × 7.5; maximum 46 mm rail length occupied

Relay rating: Do not substitute the higher contact ratings published for other 10310 ELD variants. The 10310/3/1 output is rated at 36 V DC / 30 V AC and 2 A maximum.

Choose the Correct Earth-Reference Mode

Switch 1 determines whether the -12 V earth reference is connected continuously or intermittently. Honeywell identifies DC as the normal operating position.

DC

Continuous earth-reference connection for normal monitoring.

1 Hz

Intermittent connection for circuits with solenoids or relays that could remain energized by the negative earth voltage.

1/4 Hz

Intermittent connection used for earth-fault location with a suitable current clamp.

The green MODE LED flashes at the selected frequency when the switch is set to 1 Hz or 1/4 Hz. Operating-mode selection should follow the original system design and maintenance procedures.

Earth1 / Earth2 Connections and the TEST Function

The Earth1 and Earth2 connections are significant because the TEST function can check more than the detector electronics. An internal 1.5 kΩ test path uses the Earth2 connection to help verify the earth circuit.

Earth Connection Arrangements
Separate Earth Connections
Earth1 Earth rail
Earth2 Earth rail

With independent earth leads, the preferred Honeywell wiring arrangement allows the Earth1 connection to be included in the self-test.

Single Earth Wire with Link
Earth1 / Earth2 Earth rail
One external wire Linked terminals

Linking Earth1 and Earth2 reduces wiring, but a break in the shared earth wire cannot be detected during the test.

Functional comparison only; not a field-wiring diagram. Use Honeywell's connection drawings for terminal positions and installation.

TEST

The test arrangement checks the ELD fault response and, with the separate earth connection, the associated earth circuit. A disconnected earth path can prevent the latch from setting during the test.

RESET

A latched fault can be reset using switch 2 or a high level at the reset input. The cause of the earth fault must be assessed before the equipment is returned to service.

Maintenance: Earth-fault testing, earth-wire changes and fault reset must follow the site's approved electrical and safety procedures. The preferred connection and single-wire alternative are not equally capable of detecting an open earth lead.

Installation and Exact-Part Replacement

The detector mounts on a TS35 × 7.5 DIN rail and uses a 24 V DC supply. For a replacement, compare the installed module label and hardware revision, available cabinet space, earth terminals, reset input and relay contact wiring before changing the device.

Physical and Electrical Fit

  • Complete 10310/3/1 type identification
  • TS35 DIN-rail position and access
  • +24 V, 0 V and earth connections
  • Reset and relay terminal assignments

System Verification

  • Installed safety-system design and revision
  • Selected DC / 1 Hz / 1/4 Hz mode
  • Fault indication and reset behavior
  • Approved inspection and proof-test procedure

10310/1/1, 10310/2/1 and 10310/3/1 have distinct published specifications. A similar appearance or earth-leakage function does not establish direct interchangeability. We identify quoted replacements by the exact part number and available nameplate details.

Honeywell Documentation and Related Components

Honeywell's Safety Manager Hardware Reference, section 13.3 , includes the ELD block diagram, approved connection examples and module-specific technical ratings.

Frequently Asked Questions

Is 10310-3-1 the same as 10310/3/1? +

10310/3/1 is Honeywell's type notation; 10310-3-1 is commonly used in part listings and URLs. The actual module label and revision should still be checked.

Why use separate Earth1 and Earth2 wires? +

The preferred separate-earth arrangement allows the Earth1 path to be checked during TEST. With a single linked earth wire, an open wire may go undetected by that test.

What happens to the relay after a fault? +

The relay de-energizes when an earth fault sets the internal latch. The latched state remains until a manual reset or a suitable electrical reset signal is applied.

When is 1/4 Hz mode used? +

Honeywell identifies 1/4 Hz mode for earth-fault location using a suitable current clamp. It is not the normal continuous-monitoring setting.

Can another 10310 ELD replace this module? +

Not without an engineering review. Compare the exact variant, output-contact ratings, reset interface, earth wiring, physical installation and approved system configuration before accepting a different module.

Request Honeywell 10310/3/1

Send us the exact Honeywell type number, hardware revision, required quantity, item condition and destination country. Nameplate photographs and existing ELD connection details can help confirm the requested replacement.

We confirm availability, origin, warranty and delivery terms for the specific item offered rather than treating them as fixed specifications of the module.

Submit 10310/3/1 RFQ

Hot Tags: Honeywell 10310/3/1, 10310-3-1, Honeywell earth leakage detector, 24V DC ELD, earth fault relay, Honeywell FSC parts, Safety Manager ELD, Honeywell 10310/3/1 maintenance, Honeywell FSC safety system parts, 24 V DC earth leakage detector, earth fault relay monitoring, Safety Manager ELD replacement, 10310/3/1 DIN rail detector

Hot Tags: Honeywell 10310/3/1, 10310-3-1, Honeywell earth leakage detector, 24V DC ELD, earth fault relay, Honeywell FSC parts, Safety Manager ELD, maintenance services, global sourcing, aluminum, nickel, warehousing services, valve actuators

Disclaimer:

PLCleader sells new and surplus products and develops channels for purchasing such products. This website has not been approved or recognized by any of the listed manufacturers or trademarks.

PLCleader is not an authorized distributor, dealer, or representative of the products displayed on this website. All product names, trademarks, brands, and logos used on this website are the property of their respective owners. The description, explanation, or sale of products with these names, trademarks, brands, and logos is for identification purposes only and is not intended to indicate any association with or authorization from any rights holder.